When you encounter abnormalities from the water pump that does not work and have problems with editing today P’Tank and his team would like to share information and techniques on the topic of booster pump the water pump does not work what is it? and how to fix it check booster pump not working
Water pump not working what are the causes? for example give 6 main points
- If the water level in the tank is lower than the set level both MANUAL and AUTO systems will not work. The L2 LOW LEVEL lamp will be on.
- There is no voltage supplied to the lamp control cabinet L1 (POWER) there is no light showing.
- Control fuse blown
- If the L4 or L6 (OVERLOAD) lamp is lit one or both of the pumps is overloaded.
- In the event that the voltage protection system is not complete 3 PHASE (PHASE PROTECTION), there will be a red light showing the UV position (UNDER VOLTE) indicating that the voltage is undervolted If there is a red light showing the position of UB (UNBALANCE PHASE) it indicates that the voltage is not in full phase or uneven.
Preliminary solution water pump not working that can be checked and corrected by oneself
- Check the water level in the reservoir If the water is lacking wait until the water is filled to the set level.
- Check the breaker switch to the ON position If still unable to start the machine contact the Electricity
- Check the fuse tube and measure the resistance.
- Check the 1st or 2nd pump that has a problem that is caused by the cause and after the inspection is complete RESET OVERLOAD.
- Check the phase protector inside the control cabinet measure the voltage check if the voltage comes in all 3 phases or not and check if the FUSE F1, F2, F3 is broken or not.
Before calling the service unit the preliminary examination should be done according to the above topic first.
- ALARM , LOW LEVEL
- Is there a power outage
- Is there lightning?
- Is there anyone going to repair/fix it
Caution
- Never close the suction valve while working.
- Turn off the switch before checking the motor / water pump every time.
- When there are abnormal symptoms, a skilled technician should be called to repair.
- Do not let the air in the diaphragm tank out and the pressure tank should be checked regularly every 6 months.
- No part of the system should be adjusted without information or a qualified technician.